Matelec HydroSTART FPC-82241 240v Dual Pump Controller with IP56 Steel Enclosure
Matelec HydroSTART FPC-82241 Dual Pump Controller with Capacitive Touch Interface & Current Sensing (Range 0.1-16 Amp)
| DOWNLOAD PRODUCT BROCHURE |
HydroSTART Controller Module and Metal Enclosure with Inner Door
The Matelec HydroSTART FPC-82241 is a next-generation dual pump controller designed for demanding sewage, stormwater, water transfer, pressure boosting, and hot water recirculation applications. It combines robust hardware with advanced electronics to deliver intelligent control, flexible pump sequencing, and comprehensive protection for single-phase dual pump installations.
Housed in a durable IP56-rated powder-coated mild steel enclosure with an inner door, the FPC-82241 is built for long-term outdoor performance. Its capacitive touch keypad and LED status indicators provide intuitive operation, while integrated pump current sensing delivers adjustable overload, undercurrent, and zero-current protection.
The controller supports both Level Control Mode (up to 5 float switches) and Pressure Control Mode (up to 3 pressure switches), making it adaptable to a wide variety of pumping applications. Additional smart features include duty sharing and alternation, staggered starts to prevent inrush current surges, anti-seize cycling for pumps during low use periods, and “smart chirp” alarms that automatically silence after five minutes unless muted.
TECHNICAL SPECIFICATIONS
- Model: FPC-82241
- Pumps Supported: 2 (single-phase)
- Supply Voltage: 230 VAC
- Overload Rating: Low Range (0.1–6 A) or High Range (5–16 A) selectable
- Inputs: 6x digital inputs for float/pressure switches, prime loss flow switch, or system enable
- Outputs: 2 pump supply outputs, BMS volt-free common fault output
- Communications: Modbus RTU RS485
- Enclosure Size: 400 × 300 × 150 mm
- Enclosure Rating: IP56 (outdoor, steel with inner door)
APPLICATIONS
- Sewage pump out
- Stormwater pump out
- Water transfer
- Pressure boosting
- Hot water recirculation
FEATURES
Enclosure
- Powder coated mild steel enclosure with removable gland plate
- IP54 rated with single door, for indoor mounting (Single Door version), or
- IP56 rated with inner door, for outdoor mounting (Inner Door version)
Protection
- Padlockable mains power isolator switch
- Low voltage control and input circuitry
- Individual pump circuit breaker protection/isolation
- Contactors for pump switching (three phase panels)
- Electronic short and overload protection of alarms
- Din rail mounted terminal connections
Control & interface
- HydroSTART dual pump capacitive touch keypad interface:
- Indicator lights for system and pump status, level alarm
- Buttons for alarm mute/reset and pump mode selection
- HydroSTART PCB control module with dipswitches for adjusting configuration
- Visual (strobe) and audible (buzzer) alarms
- Pump current sensing providing adjustable overload & other protections
- Soft starter per pump with adjustable soft start & stop (Soft Start versions)
Inputs
- Single phase (230Vac) power supply
- 6x digital inputs for float or pressure switches, optional prime loss flow switch and system enable
- Standard terminal setup: Low level, duty stop, duty start, standby start, high level and system enable
Outputs
- 2 pump supply outputs
Functions
- Level control mode – Level empty operation controlled by up to 5 float switches: Low level, duty stop, duty start, standby start and high level
- Pressure control mode – Pressure boost operation controlled by up to 3 pressure switches: Duty start, standby start and low pressure
- Duty sharing and alternation – Duty pump alternates on pump start and after 30 minutes of continuous running in alternation mode, or 6 hours of accumulated running in recirculation mode
- Staggered pump start – Prevents excessive current draw and reduces water surge
- Manual pump control – Manual pump mode with optional 5 minute timeout to revert to auto mode
- System enable input – Enables and disables the system in auto mode
- Static duty mode – No duty alternation, for applications using smaller duty pump that always starts first
- Smart chirp mode alarms – Audible alarm automatically silences after 5 minutes if not muted, then chirps every 5 minutes
Fault Protection
- High level alarm – Alarms after 15 minute delay with auto reset in stormwater mode, or after 1 minute with manual reset only in sewage mode
- Low level protection – Alarms and shuts down pumps on low level, manual reset only
- Low pressure protection – Alarms and shuts down pumps if low pressure input is closed for 60 seconds
- Prime loss protection – Alarms and shuts down running pumps if there is no flow for 30 seconds
- Pump anti-seize protection – Runs pumps periodically during low use to prevent seizing
- Pump current sensing – Provides adjustable pump overload, undercurrent and zero current protection