Bianco DPC1-22 NXT Dual Pump Control Panel (0.37-2.50kW 240v)
by Bianco
PN: 811199
Original price
$1,239.70
-
Original price
$1,239.70
Original price
$1,239.70
$1,239.70
-
$1,239.70
Current price
$1,239.70
Bianco DPC1-22 NXT Dual Pump Control Panel (0.37-2.50kW 240v)
DOWNLOAD PRODUCT INSTALLATION GUIDE |
The Bia nXt-DPC (Dual Pump Controller) is a module intended to control and protect a pair of single phase pumps. The user can select a control logic sequence to match their application and enjoy the benefits of superior control and protection for the pumps.
FEATURES
The Bianco nXt range of intelligent controllers are:
- Suitable for installation in various industrial and domestic applications
- Function Switches for drainage, pressure boosting and transfer applications
- User Friendly features for controlling and protecting pumps and reporting faults with live data retention
- RS485 communication interface for easy integration into Building Management Systems
- Ingress protection rating IP54 with intelligent dynamic LCD display for pump running information that is suitable for installation both indoors and outdoors
- Automatic Calibration of iCON intelligent controller which sets pump thermal overload by means of button push
- Optional enclosure with an external door available
There are 3 primary control logic modes:
- Drainage’ where control concentrated at the source
- Boosting’ which references pressure switching for control
- Transfer’ which is a mix of source and destination control
nXt-DPC has 2 x passive dry contacts and is equipped with a RS485 modbus interface to connect to a BMS
PROTECTION FUNCTIONS
Protection functions can be set, enabled or disabled independently
- Over voltage
- Under voltage
- Dry Run (under current)
- Overload (over current)
- Pump stall
- Open phase protection
- Phase reversal (3 phase models only)
- Phase in-balance (input / output)
- Pump anti-seize (96hr default)
- Manual or Automatic operation
- nXt-DPC has an audible alarm and a flashing light to indicate
- an alarm state. It supports an external alarm unit
- Fault log
- Pump accumulated running time memory
- Pump start / stop delay time setting
CONTROL INPUTS
Switched input - float, pressure switch, temperature switching
- Level probe (capacitance type probes)
OR
- 4-20mA level or pressure transmitter